FULLY AUTOMATIC AIR CONDITIONER
Trouble Diagnosis by Gauge Pressure
Connect the manifold gauge to the cooler cycle (service valve). Speculate and correct the root cause and
trouble location based on the cooler cycle pressure.
Symptom Cycle status Probable cause Corrective action
lnsufficient cooling by con-
denser
Radiator fan malfunction Repair or replace faulty parts.
Pressure retums to normal lmproper air guard attach- Clean or repair the condenser
Both high- and low-pressures when water is splashed on the ment fins.
are high. condenser. Clogged or dirty condenser
fins
Recover all refrigerant. Re-
Refrigerant over-charge vacuum and charge to appro-
priate amount.
When the compressor is
stopped, the pressure drops Recover all refrigerant. Re-
High-pressure is too high. suddenly approx. 2 kg/cm2. Air is mixed in the cooler cycle. vacuum and charge to appro-
Then, the pressure drops priate amount.
gradually.
High-pressure is high, and low- Temperature differences occurs Crushed or clogged high-pres-
pressure is too low. where the high-pressure pipe is sure pipe between the com- Repair or replace faulty part.
crushed or clogged. pressor and condenser
Clogged expansion valve
Gas leak at temperature sen- Remove foreign matter in
Evaporator outlet is not cooled. sor expansion valve, or replace.
Clogging due to foreign mat-
ter
There is a temperature differ-
Both high- and low-pressures ence at the liquid tank outlet Liquid tank malfunction Replace liquid tank.
are low. (Sometimes the low pipe, or liquid tank is covered (clogged strainer)
pressure is negative.) with frost.
Evaporator outlet pipe is cov- lmproper attachment or failure Replace intake air temperature
ered with frost (no airflow). of intake air temperature sen- sensor, or repair thermistor
sor thermistor attachment position.
There is some temperature dif- I Inspect for refrigerant leakage.
ference between compressor lnsufficient refrigerant Recover all refrigerant. Re-
high- and low-pressure pipes. vacuum and charge to appro-
priate amount.
Extract all refrigerant. Suff i-
Sometimes high-pressure is Sometimes, the evaporator out- Moisture is mixed in the cooler ciently vacuum and remove
low, and low-pressure is nega- let is not cooled. Sometimes, cycle. (Clogging due to frozen moisture. Charge to appropri-
tive. the evaporative inlet is covered moisture in the expansion ate amount. At this time,
with frost. valve) replace the liquid tank without
fail.
When the compressor is
stopped, the pressures equal- Compressor malfunction (com- I
High-pressure is low, and low- ize. There is no temperature pression defect) Replace the compressor.
pressure is high. difference between the com- Valve damage or failure
pressor high-pressure pipe and Faulty gasket
low-pressure pipe.
HA-I 0
Download PDF
Click here to download a pdf file with an instruction manual for Nissan Skyline
year of production from: 1998
Do you prefer pdf format?
Find out how to download
Enter the code to download PDF file:
All pages in one PDF file!
How to get the code?
It's very simple! Just pay through a secure PayPal payment.
It will take no longer than a few minutes.
You will receive the code immediately after payment.
The code will be displayed on the screen and will be sent to you by e-mail address.
:
Nissan Skyline R34 workshop service manual
pages 153 - 159
Nissan Skyline R34 workshop service manual
page 156 / 230
this site is maintained by advertising - for view instructions, turn off ad blocking in your browser
Download PDF
Others owner's manuals for this model: